Cable fault current calculator

Electrisim
Transformer and network
kVA
kV

Line-to-line.

%
MVA

At the transformer’s primary. Leave empty for an infinite source.

Cable
m
Ω/km

Typically 0.07–0.09 Ω/km for low-voltage multicore cables.

°C

For the minimum current (IEC 60909): 160 °C for PVC, 250 °C for XLPE.

Maximum three-phase fault current at the cable end

—

Minimum line-to-earth: —

Check the inputs: positive values, and a temperature between 20 and 400 °C.

Peak current ip at the cable end
—
Three-phase at the transformer terminals
—
Minimum line-to-earth at the cable end
—
Earth-fault loop impedance Zs
—
Cable impedance per phase at 20 °C
—
R/X at the fault (maximum case)
—

Maximum: IEC 60909 with cmax and the cable resistance at 20 °C. Minimum line-to-earth: TN system, Dyn transformer, protective conductor the same size as the phase conductors, cmin and the resistance at the end-of-fault temperature. Motor contributions are not included.

Free calculator by Electrisim · How it works