Voltage drop calculator

Electrisim
Circuit
System
V

Line-to-line for three-phase (e.g. 400 V), line-to-neutral for single-phase (e.g. 230 V).

Load given as
A
kW

Active power drawn by the load.

%
Cable
m
Conductor resistance from
°C

70 °C for PVC and 90 °C for XLPE insulation at full load.

Ω/km

AC resistance at operating temperature, from the cable datasheet.

Ω/km

Typically 0.07–0.09 Ω/km for low-voltage multicore cables.

Voltage drop

—

Drop: —

Check the inputs: every value must be a positive number.

Voltage at the load
—
Load current
—
Conductor resistance
—
Power loss in the cable
—
Loss as share of the load
—

Approximate formula from IEC 60364-5-52 (Annex G); the NEC uses the same effective-impedance approach. Accurate for drops up to about 10 %.

Free calculator by Electrisim · How it works