kVA to amps calculator
Convert between kVA, kW and amps for three-phase, single-phase and DC circuits at any voltage. Enter what you know and get the current, apparent, active and reactive power. Free, no signup.
- kVA, kW and amps, both ways
- Results update as you type
- Share any calculation as a link
Current I
—
Formula: —
Check the inputs: a positive voltage and value, and a power factor between 0 and 1.
- Current I
- —
- Apparent power S
- —
- Active power P
- —
- Reactive power Q
- —
- Rule of thumb at this voltage
- —
Balanced load. For three-phase circuits the result is the line current: the current in each cable conductor.
How the conversion works
The current follows from the apparent power and the voltage. The power factor links apparent power (kVA) and active power (kW).
- Three-phase ACI = S / (√3 · U) = P / (√3 · U · cos φ)U is the line-to-line voltage.
- Single-phase ACI = S / U = P / (U · cos φ)
- DCI = P / U
- Power triangleP = S · cos φ, Q = S · sin φ, S² = P² + Q²
Use volts with VA and W, or kilovolts with kVA and kW: the units cancel the same way.
Worked examples
| 100 kVA at 400 V, three-phase | 144.3 A |
|---|---|
| 55 kW at 400 V, three-phase, cos φ = 0.9 | 88.21 A |
| 32 A at 230 V, single-phase | 7.36 kVA |
| 2.4 kW at 48 V DC | 50 A |
For a motor, the nameplate kW is the shaft power, so divide by the efficiency as well: a 55 kW motor with 94 % efficiency draws about 93.8 A at 400 V and cos φ = 0.9.
Amps per kVA at common voltages
| Voltage | 1 kVA | 10 kVA | 100 kVA | 1000 kVA |
|---|---|---|---|---|
| 230 V single-phase | 4.348 | 43.48 | 434.8 | 4,348 |
| 400 V three-phase | 1.443 | 14.43 | 144.3 | 1,443 |
| 415 V three-phase | 1.391 | 13.91 | 139.1 | 1,391 |
| 480 V three-phase | 1.203 | 12.03 | 120.3 | 1,203 |
| 690 V three-phase | 0.8367 | 8.367 | 83.67 | 836.7 |
| 11 kV three-phase | 0.0525 | 0.5249 | 5.249 | 52.49 |
| 20 kV three-phase | 0.0289 | 0.2887 | 2.887 | 28.87 |
| 33 kV three-phase | 0.0175 | 0.1750 | 1.750 | 17.50 |
For a transformer, the rated kVA gives the full-load current on each side. The transformer full-load current calculator lists the standard sizes.
Get these formulas and more in a free two-page PDF cheat sheet
Frequently asked questions
How many amps is 1 kVA?
It depends on the voltage. At 400 V three-phase, 1 kVA is 1.443 A; at 480 V three-phase, 1.203 A; at 230 V single-phase, 4.348 A. Divide 1000 by √3 times the line-to-line voltage for three-phase, or by the voltage for single-phase.
What is the difference between kVA and kW?
kVA is apparent power, the product of voltage and current. kW is active power, the part that does useful work: kW = kVA × power factor. Cables, transformers and generators are rated in kVA because their heating depends on the current, whatever the power factor.
How do I convert kW to amps?
Divide the power in watts by √3 × U × cos φ for three-phase, or by U × cos φ for single-phase, with U in volts. For a motor, divide the nameplate kW (shaft power) by the efficiency first.
Why is there a √3 in the three-phase formula?
A balanced three-phase load takes three times the power of one phase: S = 3 · Uphase · I. With the line-to-line voltage U = √3 · Uphase, this becomes S = √3 · U · I.
Is the result the line current or the phase current?
The line current, which flows in each cable conductor. In a star-connected load it equals the phase current; in a delta-connected load the current in each branch is the line current divided by √3.