Power system glossary
Plain-language definitions of the terms you meet in load flow, short circuit, arc flash, harmonics and grid connection studies, with links to the guides and calculators that go deeper.
- 106 terms
- Every term links to a guide or calculator
- Free to read
A
- Active power (P) real power
-
The power that does useful work, measured in watts (W, kW, MW). In a three-phase system P = √3 · U · I · cos φ, with U the line-to-line voltage.
See: Power factor · Reactive power
- Adiabatic equation
-
The short-circuit check for cables, S ≥ I · √t / k, which assumes all the heat of the fault stays in the conductor. The factor k depends on the conductor and insulation (IEC 60364-4-43).
- Admittance matrix (Y-bus) bus admittance matrix
-
A square matrix that describes how the buses of a network are connected: each diagonal element is the sum of the admittances connected to a bus, and each off-diagonal element is the negative of the admittance between two buses. Load-flow and short-circuit solvers are built on it.
See: Jacobian matrix · Load flow guide
- ANDES
-
An open-source Python library for power system dynamics, developed at CURENT (University of Tennessee). Electrisim uses it for transient stability and eigenvalue analysis.
- Apparent power (S)
-
The product of voltage and current, measured in volt-amperes (VA, kVA, MVA): S² = P² + Q². Transformers, cables and generators are rated in apparent power because their heating depends on current.
See: Power factor
- Arc flash
-
The release of heat and light from an electric arc between conductors or to earth. An arc-flash study estimates the incident energy at the working distance to choose protective clothing and mark boundaries.
See: Arc flash guide · Arc flash docs
- Arc-flash boundary
-
The distance from the arc at which the incident energy falls to 1.2 cal/cm² (5.0 J/cm²), the level at which bare skin can receive a second-degree burn.
See: Arc flash guide
B
- BESS battery energy storage system
-
Batteries with a power conversion system (inverter) and usually a transformer, able to absorb or inject active and reactive power at the point of connection.
See: BESS preliminary design guide · BESS sizing guide · BESS docs
- Breaking capacity interrupting rating
-
The highest fault current a circuit breaker or fuse can interrupt safely at its rated voltage. It must be at least the prospective short-circuit current where the device is installed.
See: Short-circuit calculator · Cable fault current calculator
C
- Capacitor bank shunt capacitor
-
Capacitors connected in shunt to supply reactive power locally, raising the power factor and the voltage. Banks are often switched in steps and may be detuned with series reactors to avoid harmonic resonance.
- Charging current line charging
-
The capacitive current a cable or overhead line draws even with no load connected, because of the capacitance between its conductors and earth. Long cables produce so much reactive power that shunt reactors are often needed.
See: Ferranti effect · Shunt reactor
- CIGRE benchmark networks
-
Reference networks published by CIGRE (the International Council on Large Electric Systems) to test methods and software, such as the medium-voltage network with distributed energy resources.
See: CIGRE MV model
- Contingency analysis (N-1) N-1 security
-
Repeating the load flow with one element (line, transformer or generator) out of service at a time, to check that the network stays within thermal and voltage limits after any single outage.
See: N-1 guide
- Critical clearing time (CCT)
-
The longest time a fault can stay on the network before generators lose synchronism. If the protection clears the fault faster, the system stays transiently stable.
- Current-carrying capacity ampacity
-
The highest continuous current a cable can carry without its conductor exceeding the temperature limit of its insulation (70 °C for PVC, 90 °C for XLPE). It depends on the installation method, ambient temperature and grouping.
D
- Damping ratio
-
How quickly an oscillation dies out. For an eigenvalue σ ± jω it is ζ = −σ / √(σ² + ω²); electromechanical modes are usually expected to have a damping ratio of at least a few percent.
- Delta and star connection delta and wye
-
The two ways of connecting three-phase windings or loads. In star (wye) one end of each phase meets at a neutral point and each phase sees U/√3; in delta the phases form a loop and each sees the full line-to-line voltage.
- Distributed energy resources (DER) distributed generation
-
Small generators and storage connected to the distribution network, such as rooftop PV, batteries and small wind turbines. They change power flows and voltages in networks that were designed for one-way flow.
See: Hosting capacity · OpenDSS GUI
- Droop control
-
A control that changes one quantity in proportion to the deviation of another. Frequency droop shares active power between generators as the frequency falls; Q-V droop sets reactive power from the voltage at the point of connection.
E
- Earthing systems (TN, TT, IT) grounding systems
-
The ways a low-voltage network is connected to earth. In TN systems the source neutral is earthed and exposed metal parts connect to it through a protective conductor; in TT systems exposed parts have their own earth electrode; IT systems are isolated from earth or earthed through a high impedance.
See: Cable fault current calculator · Zero-sequence impedance
- Economic dispatch
-
Choosing the output of each generator to meet the load at the lowest cost. When network limits such as line ratings and voltages are included, it becomes an optimal power flow.
See: Optimal power flow · OPF tutorial
- Eigenvalue analysis small-signal stability
-
Linearizes the dynamic model around an operating point. The eigenvalues give the oscillation modes with their frequency and damping; modes with a negative real part decay.
- EMT simulation electromagnetic transient simulation
-
A time-domain simulation of instantaneous voltages and currents, with time steps of microseconds, used for switching transients, lightning and converter controls. It is far more detailed, and slower, than an RMS simulation.
- External grid grid equivalent, infeed
-
The network beyond the study boundary, modelled as a voltage source behind an impedance set by its short-circuit power. In a load flow it usually serves as the slack bus.
See: Slack bus · External grid docs
F
- Fault level short-circuit power, S″k
-
S″k = √3 · Un · I″k at a point in the network. A high fault level means a strong network with a low source impedance, where load changes move the voltage only a little.
- Fault ride-through (FRT) LVRT
-
The grid-code requirement that generators stay connected during voltage dips caused by network faults, defined as a voltage-against-time profile.
See: Grid code
- Ferranti effect
-
The voltage rise at the open or lightly loaded end of a long line or cable, caused by its charging current flowing through the series inductance. Shunt reactors limit it.
- Flicker
-
Rapid, repeated voltage changes that make lamps flicker visibly, caused by fluctuating loads such as arc furnaces, welders or frequently starting motors. It is measured as short-term (Pst) and long-term (Plt) severity.
See: Voltage dip · Power quality
G
- Gauss-Seidel method
-
An iterative load-flow method that updates the bus voltages one at a time. It is simple but converges slowly on large networks, so Newton-Raphson is usually preferred.
See: Newton-Raphson · Load flow guide
- Grid code
-
The technical rules a network operator sets for connecting generation and demand: reactive power capability, voltage and frequency ranges, fault ride-through and more. In the EU, the Requirements for Generators (RfG) network code sets the common framework.
See: Grid code compliance guide · Grid code P-Q docs · Wind farm reactive power guide
- Grid-forming inverter grid-following inverter
-
An inverter that sets its own voltage and frequency, like a synchronous machine, so it can support weak grids and run in an island. A grid-following inverter instead locks to the grid voltage with a phase-locked loop and injects a controlled current.
- Grid-forming converter GFM
-
A converter controlled as a voltage source: it sets its own voltage and frequency instead of following the grid, so it reacts at once to a change of load or a jump of the voltage angle. Most converters today are grid-following and need an existing voltage to synchronise to.
See: Synthetic inertia · STATCOM · Grid-forming STATCOM sizing guide
H
- Harmonic filter tuned filter, detuned filter
-
An LC circuit connected in shunt that gives harmonic currents a low-impedance path. A tuned filter absorbs a specific harmonic; a detuned filter moves the resonance below the lowest harmonic so a capacitor bank does not amplify it.
- Harmonics
-
Voltage and current components at whole multiples of the fundamental frequency (50 or 60 Hz), produced by non-linear loads such as drives, rectifiers and inverters.
See: Harmonic analysis guide · THD
- Hosting capacity
-
The amount of distributed generation a network can accept without breaking voltage, thermal or protection limits. It is usually found by adding generation in steps and repeating the load flow.
- HVDC high-voltage direct current
-
Transmission with direct current, used for long cables and for links between networks that are not synchronized. Modern links use voltage source converters.
See: VSC · Italian Hypergrid case study
I
- I″k (ikss) initial symmetrical short-circuit current
-
The RMS value of the AC part of the fault current at the moment the fault occurs (IEC 60909). Used to check breaking capacity. pandapower calls it ikss.
- ip (peak short-circuit current)
-
The highest instantaneous value of the fault current, including the DC component: ip = κ · √2 · I″k. Used to check the peak withstand and making capacity of switchgear.
- Ith (ith) thermal equivalent short-circuit current
-
The RMS current that would produce the same heat as the actual fault current over the fault duration (IEC 60909). Used to check the thermal withstand of cables and equipment.
- IEC 60909
-
The international standard for calculating short-circuit currents in three-phase AC systems, using an equivalent voltage source c · Un / √3 at the fault location.
- IEEE 1584
-
The IEEE guide for arc-flash hazard calculations. The 2018 edition gives empirical equations for arcing current and incident energy for systems from 208 V to 15 kV.
See: Arc flash guide
- IEEE 519
-
The IEEE recommended practice for harmonic control: limits for voltage distortion at the point of common coupling and for the harmonic current a customer may inject.
- Incident energy
-
The heat energy per unit area at the working distance during an arc flash, in cal/cm² or J/cm². It decides the arc rating of the protective clothing.
See: Arc flash guide · PPE category
- Inertia constant (H)
-
The kinetic energy stored in a machine’s rotating mass at rated speed divided by its rated power, in seconds. More inertia slows the change of frequency after a sudden loss of generation.
See: RoCoF · Swing equation
- Inrush current
-
The large, short current a transformer draws when it is switched on while its core saturates, often many times its rated current. Motors draw a similar high current while they start, the locked-rotor current.
- Islanding
-
Part of a network, with its own generation, that keeps running after it is disconnected from the main grid. Unintentional islands are a safety risk, so generators must detect them; planned islands can keep critical loads supplied.
J
- Jacobian matrix
-
The matrix of partial derivatives of the bus power mismatches with respect to the voltage angles and magnitudes. The Newton-Raphson load flow builds and solves it at every iteration.
See: Newton-Raphson · Admittance matrix
K
- κ (kappa) peak factor
-
The factor in ip = κ · √2 · I″k. It depends on the R/X ratio of the fault loop, κ = 1.02 + 0.98 · e−3R/X, from about 1.02 for a resistive loop to 2.0 for a purely inductive one.
L
- Load flow power flow
-
The calculation of steady-state bus voltages, branch flows and losses for given loads and generation. It is the starting point for most other studies.
See: Load flow guide
- Locked-rotor current starting current
-
The current a motor draws at standstill with full voltage applied, typically 5 to 8 times the rated current for induction motors. It causes the voltage dip when the motor starts.
M
- Monte Carlo load flow
-
Many load flows with loads and generation drawn at random from their expected ranges, to estimate how likely voltage or loading violations are.
See: Monte Carlo docs
N
- Newton-Raphson method
-
The standard iterative method for load flow. It linearizes the power-balance equations with the Jacobian matrix and usually converges in a few iterations.
See: Load flow guide
O
- Off-circuit tap changer DETC, no-load tap changer
-
A transformer tap changer that can only be moved with the transformer switched off, used to set the ratio once, for example in ±2 × 2.5 % steps. An on-load tap changer regulates the voltage in service.
See: OLTC · Transformer docs
- OLTC on-load tap changer
-
A switch on a transformer winding that changes the turns ratio while the transformer carries load, used to keep the voltage within limits.
See: Transformer docs
- OpenDSS
-
EPRI’s open-source distribution system simulator, strong in unbalanced multiphase networks, time series and harmonics. Electrisim uses it alongside pandapower.
- Optimal power flow (OPF)
-
A load flow that also chooses generator outputs and other controls to minimize cost or losses while keeping voltages and loadings within limits.
See: OPF tutorial
- Overcurrent relay IDMT relay
-
A protection relay that trips a breaker when the current exceeds a setting: instantly, after a definite time, or after an inverse time that is shorter for larger currents (IDMT curves to IEC 60255 or IEEE C37.112).
P
- pandapower
-
An open-source Python tool for power system modelling and analysis, developed by Fraunhofer IEE and the University of Kassel. Electrisim uses it for load flow, IEC 60909 short circuit, OPF and more.
- PCC / POC point of common coupling, point of connection
-
The point where a plant or customer connects to the public network. Grid-code and power-quality requirements are usually checked there.
See: Grid code
- Per-unit system p.u.
-
Expressing quantities as fractions of chosen base values for power and voltage. It keeps numbers in similar ranges and removes ideal transformers from the equivalent circuit.
See: Per-unit calculator
- Phasor
-
A complex number that represents a sinusoidal voltage or current by its RMS magnitude and phase angle at a fixed frequency. Load-flow and short-circuit calculations work with phasors.
- π model (pi model) pi equivalent
-
The equivalent circuit used for lines and cables in a load flow: a series impedance R + jX with half of the shunt capacitance at each end.
See: Line docs · Charging current
- Power factor (cos φ)
-
The ratio of active to apparent power, P / S. A low power factor means more current, and more losses, for the same useful power.
- Power quality
-
How closely the supply voltage matches an ideal sine wave at nominal magnitude and frequency. It covers harmonics, voltage dips and swells, flicker, unbalance and interruptions.
- PPE category
-
A level of arc-rated protective clothing. NFPA 70E defines categories 1 to 4 with minimum arc ratings of 4, 8, 25 and 40 cal/cm².
See: Arc flash guide
- PQ bus load bus
-
A bus where active and reactive power are specified, and the voltage magnitude and angle are calculated. Most buses in a network are PQ buses.
- P-Q capability diagram PQ diagram
-
The range of active and reactive power a generator or plant can deliver. Studies compare it at the point of connection with the grid-code requirement.
- Protection coordination selectivity, discrimination
-
Setting protective devices so that only the one closest to a fault trips, while the devices upstream wait long enough to act as backup. It is checked on time-current curves (TCC).
R
- R/X ratio X/R ratio
-
The ratio of resistance to reactance of an impedance or fault loop. It sets how fast the DC component of a fault current decays and the peak factor κ. Transformers and high-voltage lines have a low R/X (a high X/R), low-voltage cables a high one.
See: Peak factor κ
- Reactive power (Q)
-
Power that flows back and forth between source and load because of inductance and capacitance, measured in var. It does no net work but sets the voltages and adds to the current in cables and transformers.
- RMS simulation phasor simulation
-
A time-domain simulation that represents voltages and currents as phasors at the fundamental frequency, with time steps of milliseconds. It is used for transient stability, where electromechanical dynamics matter.
- RoCoF rate of change of frequency
-
How fast the system frequency changes after a sudden imbalance between generation and load, in Hz/s. It is larger in systems with less inertia, and some protection settings and grid codes limit it.
See: Inertia constant · Synthetic inertia · Grid code
S
- Short-circuit ratio (SCR)
-
The fault level at the point of connection divided by the rated power of the plant connected there. A low SCR, often taken as below about 3, marks a weak grid where voltage control and converter stability need more care.
See: Weak grid · Fault level
- Shunt reactor
-
An inductor connected from phase to earth that absorbs reactive power, used to compensate the charging current of long cables and lines.
See: Shunt docs · Ferranti effect
- Single-line diagram (SLD) one-line diagram
-
A simplified drawing of a three-phase network in which each circuit is shown as a single line. Electrisim models are drawn as single-line diagrams.
See: Diagram templates
- Slack bus swing bus, reference bus
-
The bus whose voltage magnitude and angle are fixed in a load flow. It supplies whatever power balances the network, including the losses. Usually the external grid.
See: Load flow guide · External grid
- Soft starter
-
A thyristor controller that raises the motor voltage gradually during the start, limiting the starting current, typically to 2–4 times the rated current, and the voltage dip, at the cost of lower starting torque.
- Star-delta starter wye-delta starter
-
A motor starter that connects the windings in star while starting and switches them to delta at speed. The starting current and torque drop to a third of the direct-on-line values.
- STATCOM static synchronous compensator
-
A voltage source converter that injects or absorbs reactive power to support the voltage, with a fast response that holds up well at low voltage.
See: STATCOM docs · Grid-forming converter · Grid-forming STATCOM sizing guide
- Subtransient reactance (X″d) transient reactance X′d
-
The reactance of a synchronous machine in the first cycles after a fault, set by its damper windings. It determines the machine’s initial contribution to the short-circuit current; the larger transient reactance X′d applies a little later.
- Supercapacitor ultracapacitor
-
A capacitor with a very large capacitance, thousands of farads per cell at about 2.7 V. It stores little energy (E = ½·C·V²) but delivers it at high power for seconds, which suits the short active power bursts of a grid-forming STATCOM.
See: Grid-forming converter · Grid-forming STATCOM sizing guide
- SVC static var compensator
-
Thyristor-controlled reactors and switched capacitors that provide variable reactive power for voltage control.
See: SVC docs
- Swing equation
-
The equation of motion of a synchronous machine’s rotor: the difference between mechanical and electrical power accelerates the rotor, in proportion to its inertia. Transient stability simulations solve it for every machine.
- Symmetrical components positive, negative and zero sequence
-
A method that splits any set of three unbalanced phasors into three balanced sets: positive, negative and zero sequence. Unbalanced faults are calculated by connecting the sequence networks.
- Synchronous condenser synchronous compensator
-
A synchronous machine running without a prime mover that supplies or absorbs reactive power and adds inertia and fault current to the grid. It is used to strengthen weak grids.
- Synthetic inertia virtual inertia
-
Active power that a converter delivers or absorbs in proportion to the rate of change of frequency, as the rotating mass of a synchronous machine does by itself. The power is P = 2·H·S·(df/dt)/f, so it needs an energy store on the DC side.
See: Inertia constant · RoCoF · Grid-forming STATCOM sizing guide
T
- TDD total demand distortion
-
Harmonic current distortion relative to the maximum demand load current rather than the fundamental current. IEEE 519 sets its current limits in TDD.
- THD total harmonic distortion
-
The RMS value of all harmonic components divided by the fundamental, in percent. VTHD refers to voltage and ITHD to current.
- Time series simulation
-
A sequence of load flows with loads and generation that change over time, for example 24 hourly steps for a day or 8760 for a year.
See: Time series docs
- Transient stability
-
The ability of synchronous machines to stay in step after a large disturbance such as a fault or a line trip, studied with time-domain simulation of rotor angles and voltages.
- TSO and DSO transmission and distribution system operator
-
The companies that run the high-voltage transmission grid (TSO) and the lower-voltage distribution networks (DSO). They set the grid codes and connection rules for generation and demand on their networks.
U
- uk (short-circuit voltage) impedance voltage
-
The voltage, in percent of rated voltage, that drives rated current through a transformer winding with the other winding short-circuited. It equals the transformer’s impedance in percent of its rating.
V
- Vector group
-
The code for a transformer’s winding connections and phase shift. Dyn11, for example, means a delta high-voltage winding and a star low-voltage winding with the neutral brought out, with the low-voltage side leading by 30°. It decides the zero-sequence path and so the earth-fault current.
See: 33 MW wind farm short circuit · Zero-sequence impedance
- Voltage dip voltage sag
-
A short drop in RMS voltage, for example while a large motor starts or a fault elsewhere in the network is cleared.
See: Motor starting guide
- Voltage drop
-
The difference between the voltage at the start and at the end of a cable or line, caused by the load current flowing through its impedance.
- Voltage factor c
-
An IEC 60909 factor, typically between 0.90 and 1.10, applied to the nominal voltage to cover voltage variations when calculating maximum or minimum short-circuit currents.
- Voltage stability PV curve, nose curve
-
The ability of a network to keep acceptable voltages as the load grows or after a disturbance. A PV curve plots the voltage against the transferred power; its tip, the nose, marks the maximum transfer.
See: P-V curve guide · Voltage stability docs · Reactive power
- Voltage unbalance voltage unbalance factor
-
The difference between the three phase voltages, usually given as the negative-sequence voltage in percent of the positive-sequence voltage. EN 50160 limits it to 2 % for most of the time in most public networks.
W
- Ward equivalent extended ward
-
A simple model of part of a network at a boundary bus: a constant-power load plus a constant-impedance shunt. The extended ward adds a voltage source behind an impedance.
See: Ward docs · Extended ward docs
- Weak grid
-
A grid with a low fault level compared with the connected generation or load, so its voltage changes a lot with the power flow. Plants on weak grids may need grid-forming control or extra reactive power support.
- Working distance
-
The distance from the possible arc to the worker’s face and chest, used in arc-flash calculations. IEEE 1584 gives typical values such as 455 mm for low-voltage panels and MCCs, 610 mm for low-voltage switchgear and 910 mm for medium-voltage switchgear.
See: Arc flash guide · Incident energy
Z
- Zero-sequence impedance
-
The impedance to currents that are equal and in phase in all three conductors. It governs earth-fault currents and depends on earthing and transformer connections.
See: Vector group
- ZIP load model
-
A load model that splits a load into constant-impedance (Z), constant-current (I) and constant-power (P) parts, so that its power changes with the voltage in a realistic way.