Stability analysis with ANDES
Two dynamic studies run on ANDES: transient stability simulates the response to a fault or line trip over time, and eigenvalue analysis shows how well oscillation modes are damped.
Transient Stability (ANDES Time-Domain Simulation)
ANDES
Transient Stability shows how the network responds over time to a bus fault or line trip: rotor swings, voltage recovery, and whether machines stay in synchronism. Standalone overview: Transient stability guide.
Simulate → Transient Stability (ANDES). Requires a subscription. You need at least one Generator with dynamics. An External Grid alone is not enough.
When to use
- Synchronism after a fault (speed and angle swings)
- Comparing clearing times and fault locations
- Voltage recovery after a clear or line trip
How to run
- Place a synchronous Generator and fill the Dynamics tab (defaults are applied if fields are empty).
- Click Simulate → Transient Stability (ANDES).
- Set end time, optional fault bus and clear times, and optional line outage.
- Run and inspect generator speed/angle and bus voltage vs time.
How Electrisim maps the diagram to ANDES
- Electrisim serialises the diagram (buses, lines, transformers, loads, generators) to the backend.
- The backend builds an ANDES system: static models (Bus, Line, PQ, PV/Slack) plus dynamic models (GENROU or GENCLS, exciters, governors).
- Missing Dynamics-tab fields receive textbook defaults (reported in the result).
- Optional disturbances from the study dialog: bus fault (apply/clear times) and/or a line outage at a given time.
PFlow.run()establishes the operating point;TDS.run()integrates totf.- Results return as time series: generator
ω,δ, bus voltages, and an approximate system frequency from meanω.
Input Parameters
| Parameter | Description | Type | Typical values | Default |
|---|---|---|---|---|
| Frequency | System base frequency | number | 50 or 60 Hz | 50 |
| System Base (MVA) | ANDES system MVA base for per-unit conversion | number | 100 | 100 |
| tf | Simulation end time (s) | number | 5–20 | 10 |
| Fault Bus | Bus where a three-phase fault is applied (optional) | select | Any bus on the diagram | (none) |
| fault_tf / fault_tc | Fault apply and clear times (s) | number | 1.0 / 1.1 | 1.0 / 1.1 |
| Line Outage | Optional line to trip via ANDES Toggle | select | Any AC line | (none) |
| toggle_t | Line outage time (s) | number | 2.0 | 2.0 |
Results
- Multi-series charts: generator speed
ω(pu), rotor angleδ(rad), bus voltage (pu), mean frequency (Hz) - Summary:
tf, point count, generator/bus counts, event settings - List of applied dynamic defaults and mapping warnings (e.g. skipped DC lines, static generators)
- CSV export of the time series
Requirements & Limitations (MVP)
- At least one synchronous Generator; mark one generator as slack (or include an External Grid plus generators)
- Static generators are not modelled as SynGen in this MVP (warned in results)
- Three-winding transformers and DC lines are skipped
- Full ANDES model catalogue (100+ models) is not exposed — GENROU/GENCLS, EXDC2/SEXS, TGOV1 only
Technical References
Based on: ANDES PFlow + TDS. Demo model: transient_stability_two_machine_demo.py (File → Import).
Related: Eigenvalue Analysis · Generator Dynamics tab · Motor Starting (dynamic)
Eigenvalue Analysis (ANDES Small-Signal Stability)
ANDES
Eigenvalue analysis linearises the system around the current operating point and plots modes in the complex plane: damping and oscillation frequency. Negative real parts are stable; positive real parts grow.
Simulate → Eigenvalue Analysis (ANDES). Same requirement as Transient Stability: at least one Generator with dynamics.
When to use
- Small-signal stability at the current dispatch
- Poorly damped local or inter-area modes
- Effect of inertia, droop, or exciter gains (Generator Dynamics tab)
How to run
- Use the same dynamic network as for transient stability (no fault is required).
- Click Simulate → Eigenvalue Analysis (ANDES).
- Run and inspect the s-plane plot, damping ratios, and optional participation factors.
Solver steps
- Build the ANDES system as for time-domain simulation (no fault or line-trip disturbances).
- Run power flow, then the eigenvalue study.
- Return all eigenvalues plus the least-damped oscillatory modes (frequency and damping ratio).
- Optionally include participation factors for the top modes.
Input Parameters
| Parameter | Description | Default |
|---|---|---|
| Frequency / System Base | Same as TDS (Hz / MVA) | 50 / 100 |
| n_modes | Number of least-damped oscillatory modes to highlight | 10 |
Results
- Stability verdict: stable, marginally_stable, or unstable
- Counts: positive / zero / negative eigenvalues
- s-plane scatter plot and table of σ, ω, f (Hz), damping ratio ζ
- Participation factors for highlighted modes (when available)
Technical References
Based on: ANDES eigenvalue tutorial.
Related: Transient Stability · Generator Dynamics tab