Controls
Part of the element reference. The PF, SC, OPF and MS abbreviations and the 🔴 🟡 🟢 markers in the parameter tables are explained under Element Details.
The sidebar Controls palette groups plant and feeder controllers. It uses two analysis-oriented sub-tabs:
- Steady-state — controllers that affect snapshot / control-mode load flow:
- OpenDSS: RegControl, CapControl, StorageController
- Common (pandapower & OpenDSS): Wind Turbine Controller (steady-state) (power-curve Pref)
- Pandapower: Park Controller (steady-state) (plant Q/V/PF/tanφ)
- Dynamic — time-domain controllers:
- Common: Wind Turbine Controller (dynamic) (averaging & gradient limiting)
Double-click a control on the diagram to open its parameter dialog. OpenDSS controls are created as native OpenDSS objects when you run OpenDSS load flow. Wind Turbine Controllers are applied on the frontend (they do not create OpenDSS RegControl-style objects).
Wind Turbine Controller (steady-state)
pandapower OpenDSS
Palette: Controls → Steady-state → Common. Diagram label defaults to WindTurbineController (steady-state).
Chain linked to a Wind Turbine by name:
Wind Speed Input → Lookup (Power Curve) → Pref / P
Steady-state load flow: When enabled and linked, Electrisim sets the turbine’s p_mw (Pref) from wind speed and the selected power curve, then runs the normal load flow.
When you need it vs the turbine alone: The Wind Turbine already computes p_mw from its own curve and speed. Use this controller to:
- Override wind speed on the controller (uncheck “use turbine wind speed”), or
- Use a dedicated Controller Curve instead of the turbine’s machine curve (same built-in P(v) templates as the Wind Turbine: 2.5 MW onshore, 3.3 MW onshore, 15 MW offshore).
Averaging and gradient limiting live on the separate dynamic controller.
Key parameters
| Parameter | Description | Type | Simulation Types |
|---|---|---|---|
| name | Controller name | string | đź”´ PF |
| wind_turbine | Name of the linked Wind Turbine on the diagram | string | đź”´ PF |
| enabled | When false, the controller is ignored | boolean | đź”´ PF |
| use_turbine_wind_speed | If true, Pref uses the turbine’s wind_speed_ms; if false, uses the controller’s wind speed |
boolean | đź”´ PF |
| wind_speed_ms | Controller wind speed (used when not using the turbine speed) | float | đź”´ PF |
| power_curve_type | Turbine Power Curve or Controller Curve |
string | đź”´ PF |
Engines: Pref is applied for both pandapower and OpenDSS load flow. The controller cell itself is skipped as an OpenDSS native control object.
Wind Turbine Controller (dynamic)
pandapower OpenDSS
Palette: Controls → Dynamic → Common. Diagram label defaults to WindTurbineController (dynamic).
Chain linked to a Wind Turbine by name:
Wind Speed Averaging → Gradient Limiter → Active Power Averaging
Time-domain only: Parameters are stored for RMS / transient studies. Snapshot load flow does not apply averaging or gradient limiting — use the steady-state controller (or the turbine’s own curve) for Pref.
Key parameters
| Parameter | Description | Type | Simulation Types |
|---|---|---|---|
| wind_turbine | Name of the linked Wind Turbine | string | 🟡 Dynamic |
| wind_avg_T / wind_avg_Tavg | Wind-speed averaging time constants | float | 🟡 Dynamic |
| gradient_T / gradient_max | Gradient limiter time constant and max ramp [MW/s] | float | 🟡 Dynamic |
| power_avg_T / power_avg_Tavg | Active-power averaging time constants | float | 🟡 Dynamic |
Park Controller (steady-state, pandapower)
pandapower
Station / park controller for pandapower load flow. It coordinates reactive power of linked Wind Turbines and Static Generators to meet a plant-level target. The same object is used by Grid Code Compliance (P-Q) and Grid Code Compliance (V-Q) when Plant Q dispatch is set to Park Controller (constant Q at the point of connection during the capability search).
Palette: Controls → Steady-state → Pandapower. Diagram label defaults to ParkController (steady-state).
Control modes (General tab):
- Voltage Control — hold bus voltage (optional droop: rated Q + droop %).
- Reactive Power Control — Const Q, Q(V) or Q(P) characteristic at a busbar, line, or transformer boundary.
- Power Factor Control — Const cosφ, or cosφ(P)/cosφ(V) characteristics (converted to a Q setpoint) at a busbar, line, or transformer. See cosφ(P) characteristic below.
- tan(φ) Control — Q = P × tan(φ) at a busbar, line, or transformer boundary.
Distribution: share plant Q among machines by dispatched P, rated S, Q capability (P–Q / P–U curve band at current P and terminal voltage), individual %, maximise reserve (remaining headroom on the curve), or equal shares (voltage setpoint adaption). Enable Use machine P–Q capability curves so each Wind Turbine / Static Generator Q capability tab limits park Q (clamp plant setpoint + enforce min/max Q at current P and U).
cosφ(P) characteristic
On the General tab, set PF-Control to cosphi(P)-Characteristic. Electrisim stores two branches (overexcited and underexcited). Each branch is one operating point: Min. power factor at a given Active power [MW].
| Branch (stored value) | Also shown as | Meaning (generator convention) |
|---|---|---|
| Overexcited | capacitive | Plant injects Q (Q ≥ 0). Same side as Wind Turbine Qmax / capacitive max. |
| Underexcited | inductive | Plant absorbs Q (Q < 0). Same side as Wind Turbine Qmin / inductive max. |
Excitation branch chooses which curve is used:
- Overexcited (capacitive) or Underexcited (inductive) — force that branch.
- Auto (by Q sign) — Overexcited when measured Q ≥ 0 at Control Q at, otherwise Underexcited.
The dialog labels use Overexcited / Underexcited and also show capacitive/inductive so both machine language and grid-side Q language are visible. Stored attributes remain Overexcited / Underexcited.
How it runs
- Drop a Park Controller; open it and select connected machines by name.
- Set control mode, measurement bus or boundary (line/transformer name), and setpoints / characteristic tables.
- Run pandapower Load Flow. Electrisim attaches pandapower
BinarySearchControl(andDroopControlwhen droop is enabled) and enablesrun_controlautomatically when a Park Controller is present.
Note: OpenDSS ignores Park Controllers. Balanced load flow uses positive-sequence voltage only. Sync Generators (gen) are not Q-controlled by BinarySearchControl in current pandapower — link Wind Turbines / Static Generators (sgens).
Documentation: pandapower Station Controller / BinarySearchControl
RegControl (OpenDSS)
OpenDSS
OpenDSS regulator control attached to a transformer by canvas name. Used in OpenDSS load flow (and related studies such as DG interconnection mitigations) to hold regulated voltage within a band.
Palette: Controls → Steady-state → OpenDSS.
| Parameter | Description | Type | Typical default |
|---|---|---|---|
| name | Control name | string | RegControl |
| transformer | Transformer name (or bus reference) on the diagram | string | — |
| winding | Controlled winding | integer | 2 |
| vreg | Regulated voltage [V] | float | 120 |
| band | Bandwidth [V] | float | 3 |
| ptratio / ctprim | PT ratio and CT primary [A] | float | 60 / 300 |
| delaying | Control delay [s] | float | 15 |
| enabled | Enable / disable the control | boolean | true |
Documentation: OpenDSS RegControl
CapControl (OpenDSS)
OpenDSS
OpenDSS capacitor control linked to a capacitor (or bus) by name. Switches capacitor banks based on voltage, current, kvar, or time.
Palette: Controls → Steady-state → OpenDSS.
| Parameter | Description | Type | Typical default |
|---|---|---|---|
| name | Control name | string | CapControl |
| capacitor | Capacitor name (or bus reference) | string | — |
| type | Control type | string | Voltage / Current / kvar / Time |
| on_setting / off_setting | ON / OFF thresholds (units depend on type) | float | 115 / 125 |
| ctratio / ptratio | CT / PT ratios | float | 1 / 1 |
| delay | Switching delay [s] | float | 15 |
| enabled | Enable / disable the control | boolean | true |
Documentation: OpenDSS CapControl
StorageController (OpenDSS)
OpenDSS
OpenDSS storage dispatch controller. Controlled Storage elements are exported with external dispatch mode so the controller can set charge / discharge.
Palette: Controls → Steady-state → OpenDSS.
| Parameter | Description | Type | Typical default |
|---|---|---|---|
| name | Control name | string | StorageController |
| element | Storage name(s), comma-separated | string | — |
| mode | Dispatch mode | string | PeakShave / LoadFollow / Time / Support |
| kwtarget | kW target for peak-shave / support modes | float | 0 |
| pct_reserve | Minimum state-of-charge reserve [%] | float | 20 |
| enabled | Enable / disable the control | boolean | true |
Documentation: OpenDSS Storage
Last updated: October 2026