Controls

Part of the element reference. The PF, SC, OPF and MS abbreviations and the 🔴 🟡 🟢 markers in the parameter tables are explained under Element Details.

The sidebar Controls palette groups plant and feeder controllers. It uses two analysis-oriented sub-tabs:

Double-click a control on the diagram to open its parameter dialog. OpenDSS controls are created as native OpenDSS objects when you run OpenDSS load flow. Wind Turbine Controllers are applied on the frontend (they do not create OpenDSS RegControl-style objects).

Wind Turbine Controller (steady-state)

pandapower OpenDSS

Palette: Controls → Steady-state → Common. Diagram label defaults to WindTurbineController (steady-state).

Chain linked to a Wind Turbine by name:

Wind Speed Input → Lookup (Power Curve) → Pref / P

Steady-state load flow: When enabled and linked, Electrisim sets the turbine’s p_mw (Pref) from wind speed and the selected power curve, then runs the normal load flow.

When you need it vs the turbine alone: The Wind Turbine already computes p_mw from its own curve and speed. Use this controller to:

  • Override wind speed on the controller (uncheck “use turbine wind speed”), or
  • Use a dedicated Controller Curve instead of the turbine’s machine curve (same built-in P(v) templates as the Wind Turbine: 2.5 MW onshore, 3.3 MW onshore, 15 MW offshore).

Averaging and gradient limiting live on the separate dynamic controller.

Key parameters

Parameter Description Type Simulation Types
name Controller name string đź”´ PF
wind_turbine Name of the linked Wind Turbine on the diagram string đź”´ PF
enabled When false, the controller is ignored boolean đź”´ PF
use_turbine_wind_speed If true, Pref uses the turbine’s wind_speed_ms; if false, uses the controller’s wind speed boolean 🔴 PF
wind_speed_ms Controller wind speed (used when not using the turbine speed) float đź”´ PF
power_curve_type Turbine Power Curve or Controller Curve string đź”´ PF

Engines: Pref is applied for both pandapower and OpenDSS load flow. The controller cell itself is skipped as an OpenDSS native control object.

Wind Turbine Controller (dynamic)

pandapower OpenDSS

Palette: Controls → Dynamic → Common. Diagram label defaults to WindTurbineController (dynamic).

Chain linked to a Wind Turbine by name:

Wind Speed Averaging → Gradient Limiter → Active Power Averaging

Time-domain only: Parameters are stored for RMS / transient studies. Snapshot load flow does not apply averaging or gradient limiting — use the steady-state controller (or the turbine’s own curve) for Pref.

Key parameters

Parameter Description Type Simulation Types
wind_turbine Name of the linked Wind Turbine string 🟡 Dynamic
wind_avg_T / wind_avg_Tavg Wind-speed averaging time constants float 🟡 Dynamic
gradient_T / gradient_max Gradient limiter time constant and max ramp [MW/s] float 🟡 Dynamic
power_avg_T / power_avg_Tavg Active-power averaging time constants float 🟡 Dynamic

Park Controller (steady-state, pandapower)

pandapower

Station / park controller for pandapower load flow. It coordinates reactive power of linked Wind Turbines and Static Generators to meet a plant-level target. The same object is used by Grid Code Compliance (P-Q) and Grid Code Compliance (V-Q) when Plant Q dispatch is set to Park Controller (constant Q at the point of connection during the capability search).

Palette: Controls → Steady-state → Pandapower. Diagram label defaults to ParkController (steady-state).

Control modes (General tab):

  • Voltage Control — hold bus voltage (optional droop: rated Q + droop %).
  • Reactive Power Control — Const Q, Q(V) or Q(P) characteristic at a busbar, line, or transformer boundary.
  • Power Factor Control — Const cosφ, or cosφ(P)/cosφ(V) characteristics (converted to a Q setpoint) at a busbar, line, or transformer. See cosφ(P) characteristic below.
  • tan(φ) Control — Q = P Ă— tan(φ) at a busbar, line, or transformer boundary.

Distribution: share plant Q among machines by dispatched P, rated S, Q capability (P–Q / P–U curve band at current P and terminal voltage), individual %, maximise reserve (remaining headroom on the curve), or equal shares (voltage setpoint adaption). Enable Use machine P–Q capability curves so each Wind Turbine / Static Generator Q capability tab limits park Q (clamp plant setpoint + enforce min/max Q at current P and U).

cosφ(P) characteristic

On the General tab, set PF-Control to cosphi(P)-Characteristic. Electrisim stores two branches (overexcited and underexcited). Each branch is one operating point: Min. power factor at a given Active power [MW].

Branch (stored value) Also shown as Meaning (generator convention)
Overexcited capacitive Plant injects Q (Q ≥ 0). Same side as Wind Turbine Qmax / capacitive max.
Underexcited inductive Plant absorbs Q (Q < 0). Same side as Wind Turbine Qmin / inductive max.

Excitation branch chooses which curve is used:

  • Overexcited (capacitive) or Underexcited (inductive) — force that branch.
  • Auto (by Q sign) — Overexcited when measured Q ≥ 0 at Control Q at, otherwise Underexcited.

The dialog labels use Overexcited / Underexcited and also show capacitive/inductive so both machine language and grid-side Q language are visible. Stored attributes remain Overexcited / Underexcited.

How it runs

  1. Drop a Park Controller; open it and select connected machines by name.
  2. Set control mode, measurement bus or boundary (line/transformer name), and setpoints / characteristic tables.
  3. Run pandapower Load Flow. Electrisim attaches pandapower BinarySearchControl (and DroopControl when droop is enabled) and enables run_control automatically when a Park Controller is present.

Note: OpenDSS ignores Park Controllers. Balanced load flow uses positive-sequence voltage only. Sync Generators (gen) are not Q-controlled by BinarySearchControl in current pandapower — link Wind Turbines / Static Generators (sgens).

Documentation: pandapower Station Controller / BinarySearchControl

Plant Supervisory Controller (steady-state) Sidebar: Controls → Plant Supervisory Controller

pandapower

The Plant Supervisory Controller is the leading controller of the reactive-power devices at a plant: one or more STATCOMs and switched shunt reactors. It controls reactive power or voltage at a bus you choose, typically the point of connection (for example the 400 kV POC), and coordinates the devices so the fast, continuous STATCOM does the fine control while the reactors take the bulk. It runs alongside the Park Controller, which still dispatches the wind turbines and static generators.

Where to find it

Sidebar → Controls (a collapsible list) → Plant Supervisory Controller. Drop it anywhere on the diagram; it is not wired to a bus. Double-click to open its dialog.

Dialog tabs

  • Devices — tick the STATCOMs and shunt reactors it leads. A STATCOM can be led only when both Q ratings are set and Controllable is ticked in its dialog; the list shows why one cannot be selected. Reactors show their steps and Mvar range.
  • Control — controlled bus, control mode, setpoints, and the STATCOM reserve band (% of the STATCOM rating, default 50%).

Control modes

ModeWhat it holds at the controlled bus
Q controlConstant reactive power (Mvar) flowing into the grid at the bus.
Voltage controlBus voltage at the setpoint (p.u.).
Voltage control with Q-V droopQ = Qref + (Uset − U) / droop × Qrating. The droop (%) shares voltage support with the grid instead of fixing the voltage.
cos φ controlFixed power factor at the bus, overexcited (capacitive, supplies Q) or underexcited (inductive, absorbs Q).
Q(P) characteristicQ follows a table of (P, Q) points against the active power measured at the bus. The points can be entered by hand or built from a Grid Code P-Q template: pick the template, the edge to follow (capacitive Q max or inductive Q min) and the Pmax the template's p.u. table is scaled to.

How it coordinates the devices

  1. At each control step it compares the measured quantity at the bus with the setpoint and moves the STATCOM Q. The step uses the measured sensitivity of bus Q (or voltage) to STATCOM Q, smoothed and halved after an overshoot, so it converges in a few load-flow iterations without oscillating.
  2. While the STATCOM stays inside its reserve band, the reactors are not switched. When the STATCOM leaves the band, the controller picks the reactor steps that bring it back toward the middle of its range, so it keeps dynamic reserve in both directions.
  3. The STATCOM is always held inside its Q ratings. Reactor switching is capped per load flow to avoid hunting.
  4. A voltage guard stops pushing when a led device's bus leaves 0.9…1.1 p.u.

Results

After a pandapower load flow the controller's result box shows the mode, setpoint, measured value, STATCOM Q and reactor steps, and whether the setpoint was reached. When it could not be reached, the box says why: STATCOM at its capacitive or inductive limit, or the voltage guard (low / high voltage). Led STATCOMs show Led by <controller name> in their own result boxes. Warnings are listed with the load-flow results.

Use in Grid Code Compliance (P-Q)

Select the controller in the Grid Code Compliance (P-Q) dialog. It is attached for the operating point of each sweep step. At the capability edges (Q max / Q min), the led STATCOMs are forced to their rating and the reactors are pinned to their extreme steps, so the red envelope shows the full capability.

Notes: OpenDSS ignores this controller. Led STATCOMs are modelled as PQ sources that the controller moves (see SSC). The Python export includes the controller class, so the script reproduces the Electrisim result.

RegControl (OpenDSS)

OpenDSS

OpenDSS regulator control attached to a transformer by canvas name. Used in OpenDSS load flow (and related studies such as DG interconnection mitigations) to hold regulated voltage within a band.

Palette: Controls → Steady-state → OpenDSS.

Parameter Description Type Typical default
name Control name string RegControl
transformer Transformer name (or bus reference) on the diagram string —
winding Controlled winding integer 2
vreg Regulated voltage [V] float 120
band Bandwidth [V] float 3
ptratio / ctprim PT ratio and CT primary [A] float 60 / 300
delaying Control delay [s] float 15
enabled Enable / disable the control boolean true

Documentation: OpenDSS RegControl

CapControl (OpenDSS)

OpenDSS

OpenDSS capacitor control linked to a capacitor (or bus) by name. Switches capacitor banks based on voltage, current, kvar, or time.

Palette: Controls → Steady-state → OpenDSS.

Parameter Description Type Typical default
name Control name string CapControl
capacitor Capacitor name (or bus reference) string —
type Control type string Voltage / Current / kvar / Time
on_setting / off_setting ON / OFF thresholds (units depend on type) float 115 / 125
ctratio / ptratio CT / PT ratios float 1 / 1
delay Switching delay [s] float 15
enabled Enable / disable the control boolean true

Documentation: OpenDSS CapControl

StorageController (OpenDSS)

OpenDSS

OpenDSS storage dispatch controller. Controlled Storage elements are exported with external dispatch mode so the controller can set charge / discharge.

Palette: Controls → Steady-state → OpenDSS.

Parameter Description Type Typical default
name Control name string StorageController
element Storage name(s), comma-separated string —
mode Dispatch mode string PeakShave / LoadFollow / Time / Support
kwtarget kW target for peak-shave / support modes float 0
pct_reserve Minimum state-of-charge reserve [%] float 20
enabled Enable / disable the control boolean true

Documentation: OpenDSS Storage