Motor Starting Analysis
pandapower ANDES
Motor Starting checks voltage dip and loading when asynchronous motors start. Use the steady-state study for three snapshots (before / locked-rotor / after), or the dynamic study for a time-domain startup. Methods include DOL, soft-start, star-delta, autotransformer, and reactor. Overview: Motor starting guide.
Simulate → Motor Starting. Requires a subscription. Each motor needs locked-rotor current, R/X, and rated voltage set in the Motor dialog.
When to use
- Voltage dip vs a limit (for example 10–15%) during DOL or soft-start
- Comparing starter methods in steady-state
- Start time and voltage recovery in dynamic mode
How to run
- Place Motor elements and fill locked-rotor data.
- Click Simulate → Motor Starting.
- Choose steady-state or dynamic, the motors to start, and the starter method.
- Run and review bus dip, branch loading, and (in dynamic mode) the time plots.
How the two study modes work
Steady-state (pandapower)
- Before: motors to start are taken out of service; AC load flow gives pre-start voltages.
- During: each starting motor is replaced by a locked-rotor PQ load. Starting current is \(I_{lr} = lrc\_pu \cdot I_n\), scaled by method factor \(k_m\) (DOL = 1, soft-start = \(I_{limit}/lrc\), star-delta = 1/3, autotransformer = \(tap^2\), reactor = \(1/(1+x_r)\)).
- After: motors return at their loading; post-start voltages are computed.
- Checks: dip % vs limit on every bus; branch loading during start vs thermal limit.
Dynamic (ANDES)
- Network is mapped to ANDES; selected motors become
Motor3devices withu=0. - A
Toggleconnects each motor at \(t_{start}\). - TDS returns bus voltage, motor current, slip, and torque vs time; start time is when slip falls below threshold.
- Soft-start in dynamic mode is approximated by scaling motor Sn so initial current ≈ \(I_{limit}\).
Input Parameters
| Parameter | Description | Type | Options / typical values | Default |
|---|---|---|---|---|
| Calculation Mode | Steady-state voltage dip or dynamic ANDES startup | radio | steady, dynamic | steady |
| Motor(s) to Start | Which motors start in this study | select | All in-service motors, or one motor | All |
| Starting Method | Starter type (exact factors in steady-state; DOL / approx. soft-start in dynamic) | select | DOL, soft-start, star-delta, autotransformer, reactor | DOL |
| Soft-start Current Limit (p.u.) | Current limit as multiple of rated current | number | Typical 2–4 | 3 |
| Autotransformer Tap (p.u.) | Starting tap for AT method | number | 0.1–1.0 | 0.8 |
| Reactor Reactance (p.u.) | Series reactor for reactor start | number | ≥ 0 | 0.25 |
| Max Voltage Dip Limit (%) | Pass/fail threshold for (Vbefore − Vduring) / Vbefore | number | Typical 10–15 | 15 |
| Max Branch Loading Limit (%) | Thermal check during start | number | Typical 100 | 100 |
| Dynamic t_start / t_end | Motor connect time and simulation end (dynamic mode) | number | seconds | 0.1 / 5 |
Results
- SLD boxes: bus V before/during/after and dip % (green PASS / red FAIL); motor Istart and method
- Results dialog: tables for motors, buses, branches; CSV download; Chart.js plots for dynamic mode
- Summary: worst dip, voltage/thermal fail counts
Limitations and Considerations
Important notes:
- Steady-state locked-rotor model is a snapshot, not a full torque–speed acceleration curve
- Dynamic soft-start is an approximation (Sn scaling), not a thyristor softstarter controller model
- Star-delta / autotransformer / reactor factors apply exactly in steady-state; dynamic mode uses DOL (or approx. soft-start)
- No vendor-specific DSL controllers, synchronous-motor excitation start, or variable rotor resistance
- Dynamic mode requires a network suitable for ANDES (synchronous generator / slack as for Transient Stability)
Technical References
Based on: pandapower load flow and motor element (lrc_pu, rx); ANDES Motor3 + Toggle for time-domain startup. Typical study outputs include voltage drop before/during/after start, start time, and grid loading.
Related: Motor element · Short Circuit · Transient Stability (ANDES)