Arc Flash Analysis (IEEE 1584)
pandapower
Arc Flash estimates thermal hazard at each bus: Electrisim runs a 3-phase maximum short-circuit (IEC 60909), then IEEE 1584-2018 for arcing current, incident energy, arc-flash boundary, and an NFPA 70E–style PPE category. Results are painted on the diagram. Standalone overview for search and sharing: Arc flash IEEE 1584 guide.
Simulate → Arc Flash (IEEE 1584). Requires an active subscription.
When to use
- PPE selection from incident energy
- Arc-flash boundary for labelling and approach
- Comparing LV feeder hazard (for example MCC vs a remote panel)
How to run
- Build the network and confirm short-circuit data (source impedances, transformer ratings) is filled in.
- Click Simulate → Arc Flash (IEEE 1584).
- Set working distance, electrode configuration, and clearing times, then run.
- Read incident energy, AFB, and PPE category on each applicable bus.
How it is calculated
- Short circuit: 3-phase max fault currents (Ikss) are calculated for all buses.
- Arcing current (Iarc): IEEE 1584-2018 converts bolted fault current to arcing current using electrode configuration, gap, and voltage.
- Reduced arcing current: Iarc-min is evaluated (variation factor); both clearing times are considered and the worst-case energy is kept.
- Incident energy (IE): Energy at the working distance in cal/cm², including enclosure correction factor where applicable.
- Arc-flash boundary (AFB): Distance where IE equals 1.2 cal/cm².
- PPE category: Mapped from IE using NFPA 70E thresholds (Cat 0–4 / Dangerous).
Voltage range and methods
- 208 V – 15 kV: IEEE 1584-2018 empirical model (verified open-source coefficients via
arcflash-calc). - Above 15 kV: Ralph Lee method; the result box is tagged
method: RalphLeeso HV estimates are not confused with IEEE 1584 LV/MV results. - Below 0.208 kV: Bus is skipped as outside the IEEE 1584 applicability range.
Input Parameters
| Parameter | Description | Type | Options / typical values | Default |
|---|---|---|---|---|
| Electrode Configuration | IEEE 1584 electrode geometry at the equipment | radio | VCB, VCBB, HCB, VOA, HOA | VCB |
| Working Distance (mm) | Distance from arc to worker (face/chest) | number | ≥ 305 (typical LV 455 mm, MV 610 mm) | 455 |
| Conductor Gap (mm) | Gap between electrodes | number | Typical LV ~25 mm; MV larger | 25 |
| Enclosure Height / Width / Depth (mm) | Enclosure size for correction factor (VCB, VCBB, HCB). Ignored conceptually for open-air VOA/HOA (CF = 1) | number | Typical 508 × 508 × 508 | 508 |
| Clearing Time at Iarc (s) | Protective-device clearing time at nominal arcing current | number | > 0 | 0.2 |
| Clearing Time at Iarc-min (s) | Clearing time at reduced arcing current (often longer on inverse curves) | number | > 0 | 0.2 |
Electrode configurations
- VCB — Vertical conductors in a metal box (typical switchgear / MCC)
- VCBB — Vertical conductors terminated in an insulating barrier inside a box
- HCB — Horizontal conductors in a metal box (often higher IE)
- VOA — Vertical conductors in open air
- HOA — Horizontal conductors in open air
Output Results
Each bus result box typically shows:
| Output | Description | Units |
|---|---|---|
| IE | Worst-case incident energy at the working distance | cal/cm² |
| AFB | Arc-flash boundary (IE = 1.2 cal/cm²) | mm |
| PPE | Category from IE (<1.2 → 0; 1.2–4 → 1; 4–8 → 2; 8–25 → 3; 25–40 → 4; ≥40 → Dangerous) | — |
| Ia | Arcing current used for the reported case | kA |
| Ikss | Bolted initial symmetrical short-circuit current | kA |
| method | IEEE1584-2018 or RalphLee (shown when not IEEE 1584) |
— |
Demo model
Import the industrial example arc_flash_industrial_demo.py (File → Import) to see a clear LV gradient: short cables (MCC Near) show higher IE / PPE than long feeders (Panel Far). Buses at 20 kV are labeled with the Ralph Lee method.
Limitations and Considerations
Important notes:
- Clearing times are user inputs — Electrisim does not yet read relay/fuse TCC curves automatically for this study
- Electrode configuration and enclosure dimensions are global for the run (same settings applied to all buses)
- IEEE 1584 applicability limits (voltage, Ibf, gap) are enforced with clamping/warnings where needed
- Ralph Lee results above 15 kV are conservative estimates, not IEEE 1584 PPE labels
- Always apply engineering judgment and site-specific PPE programs (NFPA 70E / local standards)
Technical References
Based on: IEEE Std 1584-2018 (Guide for Performing Arc-Flash Hazard Calculations); short-circuit currents from pandapower short-circuit; calculation library arcflash-calc (IEEE 1584-2018 implementation).
Related: Short Circuit documentation · IEEE 1584 standard