Motor starting voltage dip calculator

Estimate how far the voltage drops at the motor and at the supply bus when an induction motor starts, for direct-on-line, star-delta, autotransformer and soft starters. Free, no signup.

  • DOL, star-delta, autotransformer, soft starter
  • Results update as you type
  • Share any calculation as a link
Motor
kW
V

Line-to-line; the network voltage before the start.

%

From the datasheet, typically 6–8 for standard motors.

Typically 0.2–0.4 at locked rotor.

Starter
Method
%
× In
Supply
Supply given as
kVA
%
MVA
Cable and limit
m
Ω/km

At operating temperature, e.g. 0.232 Ω/km for 95 mm² copper at 70 °C.

Ω/km
%

Often 10–15 % at the motor terminals; check your project rules.

Voltage dip at the motor terminals

—

Voltage during the start: —

Check the inputs: positive values, power factors between 0 and 1, efficiency up to 100 %.

Voltage dip at the supply bus
—
Starting current, with the dip
—
Starting current at full voltage
—
Rated current
—
Starting power at full voltage
—
Starting torque, share of full-voltage locked-rotor torque
—
Supply impedance
—
Cable impedance
—

Steady-state estimate at the moment of starting, with the rest of the network unloaded. With star-delta, autotransformer and soft starters the voltage is on the supply side of the starter.

Add this calculator to your website

Free for any website, blog or intranet. Paste this code where the calculator should appear:

Works with WordPress (Custom HTML block), Wix, Squarespace, Webflow and plain HTML. Please keep the link under the calculator.

How the calculation works

While it starts, an induction motor behaves like a fixed impedance at a low power factor. The supply and the cable are in series with it, so the voltage divides between them: the larger the starting current, the deeper the dip.

  1. Rated and starting currentIn = P / (√3 · U · η · cos φ),  Ist = k · (ILR/In) · Ink = 1 direct on line, 1/3 star-delta, tap² for an autotransformer and Ilimit/ILR for a soft starter.
  2. Motor impedance while startingZM = U / (√3 · Ist) at cos φst
  3. Supply and cableZS = (uk/100) · U² / SrT  or  U² / S″k,  ZC = (R + jX) · L / nSplit into R and X with the X/R ratio.
  4. Voltage at the motor and dipUM / U = |ZM| / |ZS + ZC + ZM|,  dip = 1 − UM / U
  5. Starting torqueTst / TLR = kT · (UM / U)²kT = 1 direct on line, 1/3 star-delta, tap² autotransformer, (Ilimit/ILR)² soft starter.

Worked example

A 110 kW, 400 V motor (η = 95 %, cos φ = 0.86, ILR/In = 7, cos φst = 0.3) started direct on line from a 1000 kVA, 6 % transformer through 100 m of 95 mm² copper cable:

Rated current194.3 A
Starting current at full voltage1,360 A
Voltage dip at the motor12.8 %
Voltage dip at the transformer bus4.8 %
Same motor with a star-delta starter4.6 % at the motor

When one calculation is not enough

  • Other loads on the same transformer lower the voltage before the start and add to the dip.
  • How long the dip lasts depends on the load torque and inertia: that needs a dynamic run-up simulation.
  • Several motors, generators or a weak grid connection change the picture.

Electrisim’s motor starting study handles these on your whole network: steady-state with pandapower or a dynamic start with ANDES. See the motor starting guide.

Get these formulas and more in a free two-page PDF cheat sheet

Frequently asked questions

What voltage dip is acceptable when a motor starts?

There is no single limit. Common practice keeps the dip at the motor terminals within about 10–15 %, so the motor develops enough torque, and the dip at other loads lower, for example 5–10 %, so contactors hold in and lights do not flicker noticeably. Check the motor and load requirements and the network operator’s rules.

Why does a star-delta starter reduce the dip?

In star the windings see U/√3, so the line current and the starting torque both drop to a third of the direct-on-line values. The supply sees a third of the starting kVA and the dip is much smaller, but the motor must still accelerate the load with a third of the torque.

Where do I find the locked-rotor current and starting power factor?

The locked-rotor (starting) current is on the motor datasheet as IA/IN or ILR/In, typically 5–8 for standard induction motors. The starting power factor is rarely listed; 0.2–0.4 is typical, lower for large motors.

Does the calculator include the run-up time?

No. It gives the dip at the moment of starting, when the current is highest. How long the dip lasts depends on the load torque and inertia; a dynamic study, such as Electrisim’s motor starting study with ANDES, shows the run-up.

What if the motor is fed from a generator?

A generator’s transient reactance is usually much higher than a transformer’s impedance, so the dip is larger. Enter SrG / x′d as the fault level at the bus. The voltage regulator then brings the voltage back, which this estimate does not include.