IEEE 4-bus, 5-bus and 6-bus test systems for load flow and OPF

Small test systems are how load flow and optimal power flow are taught, because the results can be checked against a textbook. These three come from well-known books and papers, and their data is the same as in pandapower, MATPOWER and PYPOWER, so a result from Electrisim can be compared with any of them.

SystemSourceIn the modelDownload
4-busGrainger and Stevenson, Power System Analysis, 1994, pp. 337–338. Data from PYPOWER.4 buses at 230 kV, 4 lines, one generator, an external grid and 4 loads4-bus model
5-busLi and Bo, “Small Test Systems for Power System Economic Studies”. Data from MATPOWER.5 buses at 230 kV, 6 lines, 4 generating units, an external grid and 3 loads5-bus model
6-busWood and Wollenberg, Power Generation, Operation, and Control, 2012. Data from PYPOWER.6 buses at 230 kV, 11 lines, 2 generators, an external grid and 3 loads6-bus model

What each one is good for

  • 4-bus: load flow by hand. Small enough to follow the Newton-Raphson iterations in the book and compare every voltage and angle. The load flow guide covers the method.
  • 5-bus: economic dispatch. It was built for market and dispatch studies. Give the generators costs and run an optimal power flow to see which line limit sets the dispatch. See the OPF tutorial.
  • 6-bus: a meshed network. With 11 lines between 6 buses, taking one line out moves the power in ways that are not obvious. A good first case for N-1 contingency analysis.

Download the file, then open it in the Electrisim app with File → Import from → Device. The editor can be used without an account; running a study in the cloud needs a subscription.

Larger benchmark cases, such as the IEEE 39-bus, 118-bus and 300-bus systems, are available as templates under New diagram in the app. The data of these three is described in the pandapower documentation.

Related: the simple example network and open-source power flow tools compared with PowerFactory.